FLEXSYS SYSTEM – SUMMER/WINTER
OPERATION COMPARISON
SUMMER - FLEXSYS
COOLING
Conditioned air leaves the Variable Air Volume (VAV) air
handling unit at 15°C. The main fan inverter control
is the same as that used for any VAV system.
There is a temperature
pickup through the low to medium velocity main duct of approximately
0.5°C so air enters the raised
access floor plenum at approximately 15.5°C.
Air enters the
floor plenum through specially designed Fire dampers (FD)
and
Pressure Control Dampers (PCD’s). The PCD’s are controlled by a Modular
Integrated Terminal- Intelligent floor box (MIT-I) which holds the grille pressure
constant to make the system pressure independent. One MIT-I is used for each
pressurised plenum. Note that on all jobs to date the use of conventional fire
barriers has been eliminated.
To compensate for temperature pickup across the
floor plenum, ‘Rifle ducts’ are
used to distribute the air evenly around the floor plenum and run out between
the floor pedestals in 525mm x 225mm uninsulated ducts that sit on the floor
slab. Rifle ducts ensure the supply air temperature rise to the furthest Modular
Integrated Terminals (MIT) is limited to 1.5°C.
Air enters the space via the
MIT floor terminals. For cooling only applications these are designated MIT-C.
The amount of air supplied to the space is controlled
by the actuator and damper arrangement in each terminal. Groups of up to
14 MIT’s
are controlled by a York Flexcool zone controller and a room sensor set at
1500mm above finished floor level (FFL) to monitor the room temperature.
All
the FlexSys components are connected using York’s Plug ‘N’ Play
cable technology. Using local small power supplies ( provided by others)
the controller transforms down to a 24 volt control circuit
which connects all the
MIT’s and the Sensor to the controller. A LAN circuit is normally installed
at the same time.
All MIT terminals are fitted with a minimum fresh air
stop which can be easily altered if the occupancy level changes.
York installs
the MIT boxes into pre-cut floor tiles, provided by others,
along with all the underfloor controls and cables.
The return air leaves
the space normally though return air light fittings and
then back to the Air handling Unit.
WINTER – FLEXSYS HEATING
FlexSys can also be used to satisfy the heating requirements
in the building. This will be for the perimeter zones,
internal meeting rooms and possibly around certain types
of Atria.
MIT-G floor terminals are used for heating. These
look the same as the MIT-C unit from the occupied space,
but have
a duct spigot added to the plenum box below floor level.
One or more MIT-G terminals are connected to each side of
a Modular Fan terminal heating unit (MFT) using insulated
flexible duct.
The number of MIT terminals required and resultant
layout is normally dictated by the cooling load and the MFT
boxes
are positioned on the floor slab between the MIT-G’s.
As
the system changes from cooling to heating the cooling load
is at a minimum and the MIT dampers are shut down to
minimum fresh air. If the space temperature continues to
drop the controls will energise the heating circuit and the
MFT fan will run (it does not run in cooling mode). Air is
sucked from the room via MIT-G’s at approximately 22°C,
passing through the attached MFT’ and is redistributed
into the space via MIT-G’s. As the space temperature
continues to fall the MFT heater will be activated and raise
the supply air temperature to the space to satisfy the heat
losses.
In most buildings, and in particular Part L new build,
electric heaters controlled by current valves are used. For
applications
requiring high heating loads hot water coils are used. There
is a range of MFT’s available to satisfy varying zone
requirements.
The MFT units and associated ductwork are designed to have
a very low pressure drop.
The cooling/heating zones are controlled
by York Flexheat zone controllers and all components in the
zone are connected
using Plug ‘N’ Play cable technology as described
above.
As for FlexSys cooling above, all items are installed
by York using quick release snap connectors. |